Kyoritsu Indonesia 6050 Combi Tester

Kew Combitester provides the ultimate in Microprocessor technology
offering Loop and RCD tests with a comprehensive memory and downloading
test results ,LOOP Impedance 200/2000Ω range measurement is carried out using a test
current of 15mA. This current will not trip RCD’s rated at 30mA or
greater ,High resolution for low Loop Impedance (resolution of 0.01Ω) on 20Ω range ,Direct reading of Prospective Short Circuit Current (PSC) and earth fault current ,RCD tests at 0 and 180 degree phase angle switch permit quick tests and consistent readings ,Test of a large kind of RCD's Standard, Selective, AC and A (DC sensitive breakers) ,Constant current source circuitry ensures that a fluctuating mains voltage does not affect the accuracy of readings ,RCD Ramp test in order to indicate the actual tripping current of RCD ,Contact Voltage Reading (UC). with two selectable contact voltage limits (50 and 25V) ,Visual indication of correct wiring status and automatic lock-out if test resistors overheats ,Designed to IEC 61010-1, IEC 61557 and high protection degree IP54 ,The stored data can be transferred to PC via Optical Adapter Model 8212-RS232C and 8212-USB.
|
|
Loop Impedance Ranges (Z reading) |
20/200/2000Ω |
Loop Impedance Ranges without tripping RCDs |
200 and 2000Ω with 15mA of test current |
Max test current on Loop ranges |
3A (20Ω) / 15mA (200 and 2000Ω) |
PSC / Earth Fault Current Ranges |
200/2000A/20kA |
RCD Test AC Type (Standard and Selective) |
|× 1/2 |× 1 |× 5 Auto Ramp |
10, 30, 100, 300, 500, 1000mA 10, 30, 100, 300, 500, 1000mA 10, 30, 100mA 10, 30, 100, 300, 500mA |
RCD Test A Type (Standard and Selective) |
10, 30, 100, 300, 500mA |
RCD Test Currents multipliers |
|× 1/2, × 1, × 5 (max 1000mA type AC) (max 500mA type A) |
RCD Test Time Duration |
1000ms: × 1/2, × 1, DC 200ms: × 5, DC (500mA), and × 1 (1000mA) |
RCD Ramp Test |
From 20% to 110% of IΔn (AC type) |
Contact Voltage Block (RCD) |
50V and 25V |
Contact Voltage Reading (RCD) |
100.0V |
Phase and Earth (2 wires only) measurements |
RCD (without DC) LOOP |
Working Voltage for Loop Tests |
20Ω: 230V+10%-15% 200/2000Ω: 230V+10%-15% and 400V+10%-15% |
Working Voltage for RCD Tests |
230V+10%-15% |
Voltage Test |
100 ~ 260V (LOOP 200/2000Ω, PSC 200A:100 ~ 440V) |
Memory |
300 memory locations |
PC Software, Connection Cable |
optional with 8212-USB, 8212-RS232C |
Safety Standards |
IEC 61010-1 CAT.III 300V, IEC 61557 |
Power Source |
8 × 1.5V R6P(AA) |
Dimensions |
186(L) × 167(W) × 89(D)mm |
Weight |
980g |
Accessories Included |
Molded Plug Test Lead 7125-EU Pouch for Test Leads Instruction Manual Shoulder Strap Batteries |
Optional Accessories |
7121B (Simplified measurement probe) 8212-RS232C (RS232C adaptor with KEW Report (Software)) 8212-USB (USB adaptor with KEW Report (Software)) |
|
|